Floating Outputs

With this option, none of the outputs of the power supply is connected internally to the ground. The power supply is delivered with 2 HV shielded cords (one for the positive output, and one for the negative output).

Main specification

Diagram illustrating the operation of the option floating outputs.

With the floating option, TECHNIX provides insulation for a maximum external voltage of 10% of the full voltage range of the generator. This means that we provide an insulation of 110% of Vout max on one or the other terminals references to ground/chassis.

Here's how the formula is expressed : Vinsulation : |Vout| + |Vext|

Vout is the Output voltage of the generator

Vext is the maximum external potential introduced on one or the other pole of the generator (refered to the chassis)

 

  • For 12 kV Floating Generator with standard floating option: Diagram illustrating the operation of this option for 12kV Floating Generator with floating option.

In this example, external voltage represented in blue is introduced upon the negative terminal at the maximum value of 1200V for respecting Insulation. Voltage on positive terminal referenced to groung will vary from 1.2 to 13.2 kV.

Remark: In the case of no external Voltage is introduced, the output voltages will balance automotically at half of the Output Voltage, referenced to the chassis. We still recommend adding protections between each generator output and the chassis (transcient or varistor).

Diagram illustrating the operation of this option for0 to 12kV Generator with floating option.

At half scale, with no external voltage, the terminal voltages are automatically balanced referenced to ground.

 

For 15kV floating generator with Vext =5kVmax

This is a special floating option since the external voltage can represent more than 10 % of Vout.

Diagram illustrating the operation of this option for 0 to 15kV Generator with floating option at 5kV.If an external voltage of 5kV is introduced upon positiive terminal, V- will vary between -10kV (for Vout = 15kV) to 5kV (for Vout = 0V)

Second diagram illustrating the operation of this option for 0 to 15kV Generator with floating option at 5kV.If an external voltage of -5kV is introduced upon positive terminal, V- will vary between -5kV (for Vout = 0V) to 10kV (for Vout = 15kV)

 

 

CONTROL IS GROUND REFERENCED : with our floating option, whole electronics of control is referenced to ground and insulation is made inside of the machine providing a maximum of safety.

This allows the user to work in safety even on front panel/ in case of continuity fault of any component, there is no risk to have High Voltage or external Voltage feedback.

 

Detailed specification

Products

Discover all the associated products with this option
You need
informations ?