1
HV-Off control
Activated by a fleeting opening of the +24V
input
2
Fault status
Internal fault:
Open contact = An internal fault has been detected; +24V = No fault
output
3
Interlock status
Open contact = External interlock is open; +24V = External interlock is closed
output
4
HV-On control
Activated by a fleeting closing to +24V
input
5
Output voltage measurement
0V to 10V = 0% to 100% of max output voltage
output
475 Ω
6
Output current measurement
0V to 10V = 0% to 100% of max output current
output
475 Ω
7
Inhibit control
Activated by a digital signal between +5V to +24V
input
8
Remote control
Open contact = Local control mode; +24V = Remote control mode
input
9
External 24V reference
24V reference voltage, must be supplied by the user.
input
10
Interlock status (active low signal)
Open contact = External interlock is closed; +24V = External interlock is open
output
11
Output power measurement (option)
0V to 10V = 0% to 100% of max output power (option)
output
12
Local output voltage setting
Copy of the output voltage setting on the front panel potentiometer. 0V to 10V corresponds to 0% to 100% of max output voltage.
output
10 kΩ
13
Local output current setting
Copy of the output current setting on the front panel potentiometer. 0V to 10V corresponds to 0% to 100% of max output current.
output
10 kΩ
14
Remote output current setting
0V to 10V = 0% to 100% of max output current
input
115 kΩ
15
+10V reference
+10V reference for anologue signals, max current : 5mA
output
16
0V reference (digital signals)
0V ground reference for digital signals
output
17
Remote output voltage setting
0V to 10V = 0% to 100% of max output voltage
input
115 kΩ
18
Regulation mode status or End of Charge status
For a DC power supply:
Open contact = Current Regulation; +24V = Voltage Regulation
For a Capacitor charging power supply
Open contact = Capacitor is being charged; +24V = End of charge
output
19
HV-On status
Open contact = HV output is disabled (HV Off); +24V = HV output is enabled (HV On)
output
20
0V reference (analogue signals)
0V ground reference for analogue signals
output
21
HV On status (active low signal)
Open contact = HV output is enabled (HV On); +24V = HV output is disabled (HV Off)
output
22
External 24V reference
24V reference voltage, must be supplied by the user.
input
23
Fault status (active low signal)
Open contact = No fault; +24V = An internal fault has been detected
output
24
External interlock
Connect this pin to the digital to the 0V reference for digital signals (pin 16) to close the interlock.
input
25
+10V Reference or Remote output power setting (option)
Standard : +10V reference for anologue signals, max current : 5mA
Option: 0V to 10V = 0% to 100% of max output power
output