1
Remote control
Open contact = Local control mode; Closed contact= Remote control mode
input
2
Inhibit control
Activated by a digital signal between +5V to +24V
input
3
Output current measurement
0V to 10V = 0% to 100% of max output current
output
3.3 kΩ
4
Output voltage measurement
0V to 10V = 0% to 100% of max output voltage
output
3.3 kΩ
5
HV-On control
Produced by a fleeting closing to the digital 0V reference
input
6
Interlock status
0V = External interlock is open; +15V = External interlock is closed
output
7
Fault status
Internal Fault:
0V = An internal fault has been detected; +15V = No fault
output
8
HV-Off control
Produced by a fleeting opening from the digital 0V reference
input
9
0V reference (analogue signals)
Isolated 0V reference for analogue signals
output
10
HV-On status
0V = HV output is disabled (HV Off); +15V = HV output is enabled (HV On)
output
11
Regulation mode status or End of Charge status
For a DC power supply:
Open contact = Current Regulation; +24V = Voltage Regulation
For a Capacitor charging power supply:
Open contact = Capacitor is being charged; +24V = End of charge
output
12
Remote output voltage setting
0V to 10V = 0% to 100% of max output voltage
input
13
0V reference (digital signals)
Isolated 0V reference for digital signals
output
15
Remote output current setting
0V to 10V = 0% to 100% of max output current
input